“The transition to two-phase direct-to-chip is looming.” That’s what the Open Compute Project (OCP) stated last month as part of its overview of the current AI data center ecosystem. Of course, we’d argue that this looming transition is largely thanks to strengths of two-phase direct-to-chip (2P DTC) compared to its single-phase counterpart, like its 9-14°C greater thermal headroom and ability to cool three times more compute with the same flow. But there seems to be another key reason that two-phase adoption is arriving soon: the industry has seen that single-phase direct-to-chip (1P DTC) is about to hit a wall.

That wall largely has to do with flow rates. When a single-phase cold plate needs to remove more heat, the first move is simple: push more coolant through it. “That’s the one kind of knob that [single-phase] can turn to improve performance,” says Akshith Narayanan, Thermal Engineer at Accelsius. “But that’s proving to be pretty difficult.” Single-phase flow rates are “increasing to a point where they’re becoming untenable at a rack level.”

The industry agrees. A recent Open Compute Project whitepaper, co-authored by engineers at Oracle and Meta, puts the economic boundary of 1P DTC — the boundary at which “the full cost of running the [cooling] method turns against it,” and “where the total cost of ownership…says it is time to change” — at approximately 2100W. Next year, NVIDIA is set to release a processor with an expected heat output of 3600W.

To cool these hotter chips, the OCP paper states, single-phase coolant will have to move “beyond a point that fast flow begins to wear the channels.” Even a 1P DTC vendor acknowledges that “chip wattage may eventually become so high that pumping enough coolant per minute for heat extraction won’t be feasible.”

We’ve seen innovative modification efforts from single-phase manufacturers to extend its thermal runway — including tackling its flow rate issue. But none of these attempts can overcome the basic physics of two-phase.

The modification playbook

Single-phase vendors are attacking “all the problems you can think of,” says Qingyang Wang, Principal Engineer at Accelsius. The modification playbook includes five main moves:

  • More flow. As stated above, greater flow can buy time for single-phase; however, it also causes erosion issues in critical components, introducing greater risk for leaks and operational downtime.
  • Better materials. Vendors are thinning base plates and swapping pure copper for copper-diamond composites. However, these modifications are “common for both single-phase and two-phase cold plates,” Wang notes, which doesn’t bridge the gap between 1P vs. 2P DTC heat capture.
  • Smaller fins. Shrinking fins adds surface area to tackle heat flux issues, but it can also introduce new problems. Going “from the 100-micron standard fin size to 50” means “filtration becomes really hard,” Narayanan states, especially when dealing with a very viscous fluid like glycol.
  • Jet impingement. Some designs fire jets impinging onto the hottest part of the chip, putting more flow where it’s needed most. But this only addresses the flow rate issue locally.
  • Generative design. Engineers are using AI algorithms to generate structures that give you “the best performance without the constraints of manufacturability,” Wang says. The result is geometry “you cannot design just by engineering intuition. It must be generated.” The issue that remains to be solved, of course, is that manufacturability.

Scalability: The catch to every single-phase fix

All these advanced designs share one problem: scale. Additive manufacturing vendors are not at the scale of current skived fin efforts, Wang notes. Novel printed designs, by contrast, might come with a lot of proprietary technology specific to one or two companies, and involve concerted steps away from proven supply chains.  And in our current market, Wang states, “the cooling solution cost is less of a concern than the actual delivery lead time.”

While 1P DTC vendors may be able to scale if demand is sufficient, and advanced two-phase structures may face the same questions surrounding scalability, a clear difference remains between the two technologies: two-phase starts from a higher baseline. “Without any of these advanced heat transfer structures,” Narayanan says, “two-phase heat transfer performance is already comparable.”

Boiling remains the best

According to Narayanan and Wang, it’s well understood that the best heat transfer occurs by boiling — something that single-phase, by definition, cannot do.

The reason is latent heat. Two-phase’s boiling refrigerant absorbs heat by changing phases at a nearly constant temperature, compared to warming up the way single-phase water does. As the OCP whitepaper puts it, “two-phase operation pushes the physics boundary outward.”

Two-phase’s advantage holds wherever the industry heads next. Comparing like-for-like — whether cooling occurs in the cold plate, in a microchannel package lid, or in direct-to-die — the answer is the same: “Two-phase always has the higher heat transfer capacity potential,” Wang says, “because of its physics.”

You can’t outrun physics

Of course, single-phase isn’t expected to disappear overnight. “There are times when a very advanced single-phase cold plate can sometimes compete with a two-phase one,” Narayanan admits. And yet, even if there’s still room to improve single-phase, those improvements will at most affect its runway. Nothing can fundamentally alter its physics.

As heat flux continues to climb, and single-phase flow rates approach the point of straining critical infrastructure, data center teams planning for the next decade of GPUs and CPUs should implement the cooling method that physics favors: two-phase.